Wednesday, April 27, 2016

Types of Circuit Breaker





Many different classifications of circuit breakers can be made, based on their features such as voltage class, construction type, interrupting type, and structural features.

Low-voltage circuit breakers






                                                                                                                                                                                                                                                                                                                                                                                                                                                                                


             


An air circuit breaker for low-voltage
 (less than 1,000 volt) power distribution 
  switchgear .



Low-voltage (less than 1,000 VAC) types are common in domestic, commercial and industrial 

application, and include:

  • Miniature circuit breaker (MCB)—rated current not more than 100 A. Trip characteristics normally not adjustable. Thermal or thermal-magnetic operation. Breakers illustrated above are in this category.

There are three main types of MCBs:

  1. Type B - trips between 3 and 5 times full load current;
  2. Type C - trips between 5 and 10 times full load current;
  3. Type D - trips between 10 and 20 times full load current.

In the UK all MCBs must be selected in accordance with BS 7671.

  • Molded Case Circuit Breaker (MCCB)—rated current up to 2,500 A. Thermal or thermal-magnetic operation. Trip current may be adjustable in larger ratings.
  • Low-voltage power circuit breakers can be mounted in multi-tiers in low-voltage switchboards or switchgear cabinets.
The characteristics of low-voltage circuit breakers are given by international standards such as IEC 947. These circuit breakers are often installed in draw-out enclosures that allow removal and interchange without dismantling the switchgear.
Large low-voltage molded case and power circuit breakers may have electric motor operators so they can open and close under remote control. These may form part of an automatic transfer switch system for standby power.
Low-voltage circuit breakers are also made for direct-current (DC) applications, such as DC for subway lines. Direct current requires special breakers because the arc is continuous—unlike an AC arc, which tends to go out on each half cycle. A direct current circuit breaker has blow-out coils that generate a magnetic field that rapidly stretches the arc. Small circuit breakers are either installed directly in equipment, or are arranged in a breaker panel.
TheDIN rail-mounted thermal-magnetic miniature circuit breaker is the most common style in modern domestic consumer units and commercial electricaldistribution boards throughout Europe. The design includes the following components:
  1. Actuator lever  - used to manually trip and reset the circuit breaker. Also indicates the status of the circuit breaker (On or Off/tripped). Most breakers are designed so they can still trip even if the lever is held or locked in the "on" position. This is sometimes referred to as "free trip" or "positive trip" operation.
  2. Actuator mechanism - forces the contacts together or apart.
  3. Contacts - allow current when touching and break the current when moved apart.
  4. Terminals
  5. Bimetallic strip - separates contacts in response to smaller, longer-term overcurrents
  6. Calibration screw - allows the manufacturer  to precisely adjust the trip current of the device after assembly.
  7. Solenoid - separates contacts rapidly in response to high overcurrents
  8. Arc divider/extinguisher 

Magnetic circuit breakers 

Magnetic circuit breakers use a solenoid ( electomagnet ) whose pulling force increases with the current . Certain designs utilize electromagnetic forces in addition to those of the solenoid. The circuit breaker contacts are held closed by a latch. As the current in the solenoid increases beyond the rating of the circuit breaker, the solenoid's pull releases the latch, which lets the contacts open by spring action. Some magnetic breakers incorporate a hydraulic time delay feature using a viscous fluid. A spring restrains the core until the current exceeds the breaker rating. During an overload, the speed of the solenoid motion is restricted by the fluid. The delay permits brief current surges beyond normal running current for motor starting, energizing equipment, etc. Short circuit currents provide sufficient solenoid force to release the latch regardless of core position thus bypassing the delay feature. Ambient temperature affects the time delay but does not affect the current rating of a magnetic breaker


Thermal magnetic circuit breakers


Thermal magnetic circuit breakers, which are the type found in most distribution boards, incorporate both techniques with the electromagnet responding instantaneously to large surges in current (short circuits) and the bimetallic strip responding to less extreme but longer-term over-current conditions. The thermal portion of the circuit breaker provides an "inverse time" response feature, which trips the circuit breaker sooner for larger overcurrents but allows smaller overloads to persist for a longer time. On very large over-currents during a short-circuit, the magnetic element trips the circuit breaker with no intentional additional delay.


Common trip breakers






When supplying a branch circuit with more than one live conductor, each live conductor must be protected by a breaker pole. To ensure that all live conductors are interrupted when any pole trips, a "common trip" breaker must be used. These may either contain two or three tripping mechanisms within one case, or for small breakers, may externally tie the poles together via their operating handles. Two-pole common trip breakers are common on 120/240-volt systems where 240 volt loads (including major appliance or further distribution boards) span the two live wires. Three-pole common trip breakers are typically used to supply three-phase electric power to large motors or further distribution boards.

Two- and four-pole breakers are used when there is a need to disconnect multiple phase AC, or to disconnect the neutral wire to ensure that no current flows through the neutral wire from other loads connected to the same network when workers may touch the wires during maintenance. Separate circuit breakers must never be used for live and neutral, because if the neutral is disconnected while the live conductor stays connected, a dangerous condition arises: the circuit appears de-energized (appliances don't work), but wires remain live and some RCDs may not trip if someone touches the live wire (because some RCDs need power to trip). This is why only common trip breakers must be used when neutral wire switching is needed.



Medium-voltage circuit breakers










Medium-voltage circuit breakers rated between 1 and 72 kV may be assembled into metal-enclosed switchgear line ups for indoor use, or may be individual components installed outdoors in a substation. Air-break circuit breakers replaced oil-filled units for indoor applications, but are now themselves being replaced by vacuum circuit breakers (up to about 40.5 kV). Like the high voltage circuit breakers described below, these are also operated by current sensing protective relays operated through current transformer . The characteristics of MV breakers are given by international standards such as IEC 62271. Medium-voltage circuit breakers nearly always use separate current sensors and protective relays, instead of relying on built-in thermal or magnetic overcurrent sensors.

Medium-voltage circuit breakers can be classified by the medium used to extinguish the arc:

  • Vacuum circuit breakers—With rated current up to 6,300 A, and higher for generator circuit breakers. These breakers interrupt the current by creating and extinguishing the arc in a vacuum container - aka "bottle". Long life bellows are designed to travel the 6–10 mm the contacts must part. These are generally applied for voltages up to about 40,500 V.  which corresponds roughly to the medium-voltage range of power systems. Vacuum circuit breakers tend to have longer life expectancies between overhaul than do air circuit breakers.
  • Air circuit breakers—Rated current up to 6,300 A and higher for generator circuit breakers. Trip characteristics are often fully adjustable including configurable trip thresholds and delays. Usually electronically controlled, though some models are microprocessor controlled via an integral electronic trip unit. Often used for main power distribution in large industrial plant, where the breakers are arranged in draw-out enclosures for ease of maintenance.
  • SF6 circuit breakers extinguish the arc in a chamber filled with sulfure hexafluoride gas.

Medium-voltage circuit breakers may be connected into the circuit by bolted connections to bus bars or wires, especially in outdoor switchyards. Medium-voltage circuit breakers in switchgear line-ups are often built with draw-out construction, allowing breaker removal without disturbing power circuit connections, using a motor-operated or hand-cranked mechanism to separate the breaker from its enclosure. Some important manufacturer of VCB from 3.3 kV to 38 kV are ABB, Eaton, Siemens, HHI(Hyundai Heavy Industry), S&C Electric Company, Jyoti and BHEL.



High-voltage circuit breakers







Electrical power transmission networks are protected and controlled by high-voltage breakers. The definition of high voltage varies but in power transmission work is usually thought to be 72.5 kV or higher, according to a recent definition by the International Electrotechnical Commition (IEC). High-voltage breakers are nearly always solenoid-operated, with current sensing protective relay operated through current transformers. In substations the protective relay scheme can be complex, protecting equipment and buses from various types of overload or ground/earth fault.

High-voltage breakers are broadly classified by the medium used to extinguish the arc.

  • Bulk oil
  • Minimum oil
  • Air blast
  • Vacuum
  • SF6
  • Co2

Due to environmental and cost concerns over insulating oil spills, most new breakers use SF6 gas to quench the arc.

Circuit breakers can be classified as live tank, where the enclosure that contains the breaking mechanism is at line potential, or dead tank with the enclosure at earth potential. High-voltage AC circuit breakers are routinely available with ratings up to 765 kV. 1,200 kV breakers were launched by Siemens in November 2011, followed by ABB in April the following year.

High-voltage circuit breakers used on transmission systems may be arranged to allow a single pole of a three-phase line to trip, instead of tripping all three poles; for some classes of faults this improves the system stability and availability.

Hgh voltage direct current  circuit breakers are still a field of research as of 2015. Such breakers would be useful to interconnect HVDC transmission systems.


Sulfur hexafluoride (SF6) high-voltage circuit breakers


A sulfur hexafluoride circuit breaker uses contacts surrounded by sulfur hexafluoride gas to quench the arc. They are most often used for transmission-level voltages and may be incorporated into compact gas-insulated switchgear. In cold climates, supplemental heating or de-rating of the circuit breakers may be required due to liquefaction of the SF6 gas.


Disconnecting circuit breaker (DCB)






The disconnecting circuit breaker (DCB) was introduced in 2000 and is a high-voltage circuit breaker modeled after the SF6-breaker. It presents a technical solution where the disconnecting function is integrated in the breaking chamber, eliminating the need for separate disconnectors. This increases the availability , since open-air disconnecting switch main contacts need maintenance every 2–6 years, while modern circuit breakers have maintenance intervals of 15 years. Implementing a DCB solution also reduces the space requirements within the substation, and increases the reliability, due to the lack of separate disconnectors.

In order to further reduce the required space of substation, as well as simplifying the design and engineering of the substation, a fiber optic current sensor (FOCS) can be integrated with the DCB. A 420 kV DCB with integrated FOCS can reduce a substation’s footprint with over 50% compared to a conventional solution of live tank breakers with disconnectors and current transformers, due to reduced material and no additional insulation medium.



Carbon dioxide (CO2) high-voltage circuit breakers




In 2012 ABB presented a 75 kV high-voltage breaker that uses carbon dioxide as the medium to extinguish the arc. The carbon dioxide breaker works on the same principles as an SF6 breaker and can also be produced as a disconnecting circuit breaker. By switching from SF6 to CO2 it is possible to reduce the CO2 emissions by 10 tons during the product’s life cycle.




follow us :

https://www.youtube.com/channel/UC8uzr-PXQxLpAiVKA7S1rRQ?disable_polymer=true


https://www.facebook.com/Engi.Prog/?ref=bookmarks

!!?? What is the circuit breaker and his Operation

A circuit breaker is an automatically operated electric switch designed to protect an electrical circuit from damage caused by over current or short circuit . Its basic function is to interrupt current flow after protective relays detect a fault. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation.
 Circuit breakers are made in varying sizes, from small devices that protect an individual household appliance up to large switch gear designed to protect high voltage circuits feeding an entire city.
 The generic function of a circuit breaker, RCD or a fuse, as an automatic means of removing power from a faulty system is often abbreviated to ADS ( Automatic Disconnection of Supply).

Operation of circuit breaker

All circuit breaker systems have common features in their operation. Although details vary substantially depending on the voltage class, current rating and type of the circuit breaker.

The circuit breaker must detect a fault condition; in low voltage circuit breakers this is usually done within the breaker enclosure. Circuit breakers for large currents or high voltages are usually arranged with protective relay pilot devices to sense a fault condition and to operate the trip opening mechanism. The trip solenoids that releases the latch is usually energized by a separate battery, although some high-voltage circuit breakers are self-contained with current transformers , protective relay  and an internal control power source.

Once a fault is detected, the circuit breaker contacts must open to interrupt the circuit; some mechanically-stored energy (using something such as springs or compressed air) contained within the breaker is used to separate the contacts, although some of the energy required may be obtained from the fault current itself. Small circuit breakers may be manually operated, larger units have solenoid to trip the mechanism, and electric motors to restore energy to the springs.

The circuit breaker contacts must carry the load current without excessive heating, and must also withstand the heat of the arc produced when interrupting (opening) the circuit. Contacts are made of copper or copper alloys, silver alloys and other highly conductive materials. Service life of the contacts is limited by the erosion of contact material due to arcing while interrupting the current. Miniature and molded-case circuit breakers are usually discarded when the contacts have worn, but power circuit breakers and high-voltage circuit breakers have replaceable contacts.

When a current is interrupted, an arc is generated. This arc must be contained, cooled and extinguished in a controlled way, so that the gap between the contacts can again withstand the voltage in the circuit. Different circuit breakers use vaccum , air,insulating gas or oil as the medium the arc forms in. Different techniques are used to extinguish the arc including:

  • Lengthening / deflection of the arc
  • Intensive cooling (in jet chambers)
  • Division into partial arcs
  • Zero point quenching (Contacts open at the zero current time crossing of the Ac waveform, effectively breaking no load current at the time of opening. The zero crossing occurs at twice the line frequency, i.e. 100 times per second for 50 Hz and 120 times per second for 60 Hz AC)
  • Connecting capacitors in parallel with contacts in Dc circuits.

Finally, once the fault condition has been cleared, the contacts must again be closed to restore power to the interrupted circuit.

Types of circuit breakers

  • Low-voltage circuit breakers
  • Medium-voltage circuit breakers
  • High-voltage circuit breakers


follow us :
https://www.youtube.com/channel/UC8uzr-PXQxLpAiVKA7S1rRQ?disable_polymer=true

https://www.facebook.com/Engi.Prog/?ref=bookmarks

Saturday, April 23, 2016

Types Of Generators and equivalent circuits


Electromagnetic generators fall into one of two broad categories, dynamos and alternators
Dynamo generate direct current , usually with voltage or current fluctuations, usually through the use of a commutator 
Alternator generate Alternating current , which may be rectified by another (external or directly incorporated) system
Mechanical
Rotor : The rotating part of an electrical machine 
Stator : The stationary part of an electrical machine

 Electrical 
Armature : The power-producing component of an electrical machine. In a generator, alternator, or dynamo the armature windings generate the electric current. The armature can be on either the rotor or the stator
Field : The magnetic field component of an electrical machine. The magnetic field of the dynamo or alternator can be provided by either electromagnets or permanent magnets mounted on either the rotor or the stator

History
         Before the connection between magnetism and electricity  was discovered, electrostatic generator were used. They operated on electrostatic principles. Such generators generated very high voltage and lowcurrent . They operated by using moving electricaly charged belts, plates, and disks that carried charge to a high potential electrode. The charge was generated using either of two mechanisms: Electrostatic induction and the Triboelectric effect . Because of their inefficiency and the difficulty of insulating machines that produced very high voltages, electrostatic generators had low power ratings, and were never used for generation of commercially significant quantities of electric power, even at the time of its development

Theoretical development



The operating principle of electromagnetic generators was discovered in the years of 1831–1832 by Michael Faraday . The principle, later called Faradays law , is that an Electromotive force is generated in an electrical conductor which encircles a varying Magnetic flux 
He also built the first electromagnetic generator, called theFaraday disk , a type of homopolar generator , using a copper disc rotating between the poles of a horseshoe magnet It produced a small Dc voltage 
This design was inefficient, due to self-cancelling counterflows of current in regions that were not under the influence of the magnetic field. While current was induced directly underneath the magnet, the current would circulate backwards in regions that were outside the influence of the magnetic field. This counterflow limited the power output to the pickup wires, and induced waste heating of the copper disc. Later homopolar generators would solve this problem by using an array of magnets arranged around the disc perimeter to maintain a steady field effect in one current-flow direction
Another disadvantage was that the output voltage was very low, due to the single current path through the magnetic flux. Experimenters found that using multiple turns of wire in a coil could produce higher, more useful voltages. Since the output voltage is proportional to the number of turns, generators could be easily designed to produce any desired voltage by varying the number of turns. Wire windings became a basic feature of all subsequent generator designs
Independently of Faraday, the HungarianAnyos Jedlik started experimenting in 1827 with the electromagnetic rotating devices which he called electromagnetic self-rotors . In the prototype of the single-pole electric starter (finished between 1852 and 1854) both the stationary and the revolving parts were electromagnetic. He also may have formulated the concept of the dynamo in 1861 (before siemens and Weatstone ) but didn't patent it as he thought he wasn't the first to realize this

Direct current generators



The dynamo was the first electrical generator capable of delivering power for industry. The dynamo uses electromagnetic induction to convert mechanical rotation into Direct Current through the use of a commutator . An early dynamo was built by Hippolyte Pixii in 1832

The Woolrich Electrical Generator  of 1844, now in Thinktank,Birmingham science museum , is the earliest electrical generator used in an industrial process It was used by the firm of Elkingtons for commercial Electroplating
The modern dynamo, fit for use in industrial applications, was invented independently by sir Charles  Weatstone werner von siemens and Samuel Alfred Varley. Varley took out a patent on 24 December 1866, while Siemens and Wheatstone both announced their discoveries on 17 January 1867, the latter delivering a paper on his discovery to the Royal Society 
The "dynamo-electric machine" employed self-powering electromagnetic field coils rather than permanent magnets to create the stator field.Wheatstone's design was similar to Siemens', with the difference that in the Siemens design the stator electromagnets were in series with the rotor, but in Wheatstone's design they were in parallel. The use of electromagnets rather than permanent magnets greatly increased the power output of a dynamo and enabled high power generation for the first time. This invention led directly to the first major industrial uses of electricity. For example, in the 1870s Siemens used electromagnetic dynamos to power electric arc furnaces for the production of metals and other materials
The dynamo machine that was developed consisted of a stationary structure, which provides the magnetic field, and a set of rotating windings which turn within that field. On larger machines the constant magnetic field is provided by one or more electromagnets, which are usually called field coils
Large power generation dynamos are now rarely seen due to the now nearly universal use of alternating current  for power distribution. Before the adoption of AC, very large direct-current dynamos were the only means of power generation and distribution. AC has come to dominate due to the ability of AC to be easily transformed  to and from very high voltages to permit low losses over large distances

Alternating current generators



Through a series of discoveries, the dynamo was succeeded by many later inventions, especially the AC alternator which was capable of generating alternating current 
Alternating current generating systems were known in simple forms from Michael Faraday'original discovery of the Magnetic induction of electric current . Faraday himself built an early alternator. His machine was a "rotating rectangle", whose operation was heteropolar - each active conductor passed successively through regions where the magnetic field was in opposite directions
Large two-phase alternating current generators were built by a British electrician J.E.H Gordon, in 1882. The first public demonstration of an "alternator system" was given by William stanly,Jr an employee of westinghouse electric in 1886.
sebastian ziani de Ferranti established Ferranti, Thompson and Ince in 1882, to market his Ferranti-Thompson Alternator, invented with the help of renowned physicist lord Kelvin His early alternators produced frequencies between 100 and 300 HZ. Ferranti went on to design the Deptford power station for the London Electric Supply Corporation in 1887 using an alternating current system. On its completion in 1891, it was the first truly modern power station, supplying high-voltage AC power that was then "stepped down" for consumer use on each street. This basic system remains in use today around the world

 : Specialized types of generator

 Direct current

- Homo-polar generator


A homo polar generator is a Dc electrical generator comprising an electrically conductive disc or cylinder rotating in a plane perpendicular to a uniform static magnetic field. A potential difference is created between the center of the disc and the rim (or ends of the cylinder), the electrical polarity depending on the direction of rotation and the orientation of the field
It is also known as a unipolar generatoracyclic generatordisk dynamo, or Faraday disc. The voltage is typically low, on the order of a few volts in the case of small demonstration models, but large research generators can produce hundreds of volts, and some systems have multiple generators in series to produce an even larger voltage .They are unusual in that they can produce tremendous electric current, some more than a million amperes , because the homopolar generator can be made to have very low internal resistance

MHD generator -


A magnetohydrodynamic generator directly extracts electric power from moving hot gases through a magnetic field, without the use of rotating electromagnetic machinery. MHD generators were originally developed because the output of a plasma MHD generator is a flame, well able to heat the boilers of a steam power plant . The first practical design was the AVCO Mk. 25, developed in 1965. The U.S. government funded substantial development, culminating in a 25 MW demonstration plant in 1987. In the soviet union from 1972 until the late 1980s, the MHD plant U 25 was in regular commercial operation on the Moscow power system with a rating of 25 MW, the largest MHD plant rating in the world at that time. MHD generators operated as a topping cycle are currently (2007)    less efficient than combined cycle gas turbines 


 : Alternating current



Induction generator -


Some Ac motors may be used as generators, turning mechanical energy into electric current. Induction generators operate by mechanically turning their rotor faster than the synchronous speed, giving negative slip. A regular AC asynchronous motor usually can be used as a generator, without any internal modifications. Induction generators are useful in applications such as minihydro power plants, wind turbines, or in reducing high-pressure gas streams to lower pressure, because they can recover energy with relatively simple controls
To operate, an induction generator must be excited with a leading voltage; this is usually done by connection to an electrical grid, or sometimes they are self-excited by using phase correcting capacitors

Linear electric generator - 


In the simplest form of linear electric generator, a sliding magnet moves back and forth through a solenoid - a spool of copper wire. An alternating current is induced in the loops of wire by Faradays law of induction each time the magnet slides through. This type of generator is used in theFaraday flashlight . Larger linear electricity generators are used inwave power schemes


Variable speed constant frequency generators -


Many renewable energy  efforts attempt to harvest natural sources of mechanical energy (wind, tides, etc.) to produce electricity. Because these sources fluctuate in power applied, standard generators using permanent magnets and fixed windings would deliver unregulated voltage and frequency. The overhead of regulation (whether before the generator via gear reduction or after generation by electrical means) is high in proportion to the naturally-derived energy available
New generator designs such as the asynchronous or induction singly-fed generator  , the doubly fed generator, or the bruchless wound-rotor doubly fed generator are seeing success in variable speed constant frequency applications, such as wind turbines or other renewable energy technologies . These systems thus offer cost, reliability and efficiency benefits in certain use cases 

Equivalent circuit

An equivalent circuit of a generator and load is shown in the diagram to the right. The generator is represented by an abstract generator consisting of an ideal voltage source  and an internal resistance. The generator's V_G and R_G parameters can be determined by measuring the winding resistance (corrected to operating temperture), and measuring the open-circuit and loaded voltage for a defined current load
This is the simplest model of a generator, further elements may need to be added for an accurate representation. In particular, inductance can be added to allow for the machine's windings and  magnetic leakage flux, but a full representation can become much more complex than this




follow us :
https://www.youtube.com/channel/UC8uzr-PXQxLpAiVKA7S1rRQ?disable_polymer=true

https://www.facebook.com/Engi.Prog/?ref=bookmarks

CONTROL TRANSFORMER

The function of a control transformer is to obtain the desired low voltage control supply from the power supply system. The stepped ...